Venting Change for Marey Power Gas Models GA5L/10L/16L

GlobalTowne is an authorized distributor of the Marey gas and electric tankless water heaters.  Marey has recently updated their manual for the power gas GA5L/10L and 16L units.  The installation manual has been revised to show that the 5L/10L and 16L power gas units must be vented vertically up through the roof.  The minimum vertical vent height shall be no less than 6'. Sidewall venting on a naturally drafting unit is not permissible and is against the National Fuel Gas Code (NFGC).  Below is a diagram that shows the vertical venting and also the venting specifications for each unit. 
Venting Specifications for:
Marey Power Gas GA5L - Uses 4" diameter double walled galvanized type B-vent

Marey Power Gas GA10L - Uses 4" diameter double walled galvanized type B-vent

Marey Power Gas GA16L - Uses 5" diameter double walled galvanized type B-vent

For further questions on the Marey products please call GlobalTowne at 888-726-9752.